1. DC Test
Note that a squirrel-cage induction machine has only stator terminals accessible.
- Turn on the low-power DC power supply and limit the current to 1.8 A.
- Turn the supply off.
- Connect the supply terminals across two of the induction motor terminals (labeled A, B, and C).
- Turn the supply on and record the output voltage and current.
- Repeat for the two other phase combinations.
- Note that the measured resistance is for two phases in series, thus the per-phase resistance is half the measurement.
2. No-Load Test
Test the induction machine with no load to find the per-phase magnetizing branch parameters Xm and RC. For this test, make sure the load dynamometer has all its terminals disconnected, where it is generating no power and supporting no load.
- Make sure the three-phase source is off.
- Check that the VARIAC is at 0% and then wire the VARIAC to the three-phase outlet, and connect the setup (Fig. 1).
- Double-check that the circuit connections are as shown in Fig. 1, and then turn on the three-phase source.
- Quickly increase the VARIAC output until each of the digital power meters reads around 208 V.
- Record the power, voltage, and current readings from both meters.
- Measure the speed using the strobe light (tune the strobe light to a reasonable speed), and label the measurement as ωo.
- Record the torque reading in N·m or lb·ft, and label the measurement as To just in case the torque transducer or torque-measuring apparatus is not well calibrated. This is the no-load torque.
- Set the VARIAC back to 0% then turn off the three-phase source. Leave the rest of the circuit intact.

Figure 1: Electrical setup for no-load test. Please click here to view a larger version of this figure.
3. Locked-Rotor Test
Test the induction machine with a locked rotor in a manner similar to the short-circuit test of a transformer. Use this test to find the per-phase series resistances and leakage inductances. For this test, make sure the load dynamometer has all its terminals disconnected.
- Make sure the three-phase source is off.
- Check that the VARIAC is at 0%.
- Lock the rotor on the dynamometer side using a mechanical clamp or a zero-torque setting, if the dynamometer is digitally controlled.
- Note that the setup is still similar to that of Fig. 1, except with a locked rotor.
- Double-check that the circuit connections are as shown in Fig. 2.
- Turn on the three-phase source and the induction machine switch.
- Slowly and carefully increase the VARIAC until rated current is reached on one or both of the digital power meters.
- Record the power, voltage, and current readings from both meters.
- Set the VARIAC back to 0% then turn off the three-phase source. Leave the rest of the circuit intact.

Figure 2: Setup for load test.
4. Load Test
Use this test to trace the linear torque-speed characteristic of the induction machine. For this test, use the dynamometer with a shunt-field as a generator (more on this operating condition is given later in the DC machines video, but the armature is the generator output port).
- Make sure the three-phase source and induction machine switch are off.
- Check that the VARIAC is at 0%.
- Remove the locking clamp from the rotor shaft.
- Connect the circuit (Fig. 2). Use RL=300Ω but keep SD off.
- Do not use the series field.
- Check the circuit, then turn on the three-phase source and the induction machine switch.
- Quickly increase the VARIAC output until each of the digital power meters reads around 208 V.
- Record the power, voltage, and current readings from both meters.
- Measure the speed and label it as ω1. To measure the speed, adjust the "Coarse" frequency knob on the strobe light until the shaft looks almost stationary, and then fine-tune the frequency setting using the "Fine" knob.
- Record the torque reading and label it as T1.
- Note that this operating point (ω1, T1) is not the same as no load, because the field winding is also acting as a load in parallel with the armature. As SD is turned later and RL is decreased, the load is increased since the load current increases as RL decreases.
- Turn on SD. Measure the speed and label it as ω2.
- Record the torque reading and label it as T2.
- Turn off SD. Change RL to 200 Ω, then turn on SD.
- Measure the speed and label it as ω3.
- Record the torque reading and label it as T3.
- Turn on SD. Change RL to 100 Ω. Turn on SD.
- Measure the speed and label it as ω4.
- Record the torque reading and label it as T4.
- Set the VARIAC to 0%, turn off the three-phase source, and disassemble the circuit.